• Norah (pup/it/she)@lemmy.blahaj.zone
    link
    fedilink
    English
    arrow-up
    3
    ·
    5 hours ago

    No, it’s not the only wire in the circuit. If that plug is plugged into an outlet, then the hot live wire is coming into the circuit at the pin labelled live, and connecting to the ground wire of the device. That ground wire is usually connected to the metal frame of an appliance. Because of the white wire connecting the live and neutral pins together, it’s going to immediately flow back to the breaker box. However, if for whatever reason the path from the ground of the device to actual ground is shorter, then the electricity will flow through the device. It is possible for a person to be in the path to ground. The way this is wired might also circumnavigate an RCD, preventing the safety switch from operating correctly.

    • Ilovethebomb@sh.itjust.works
      link
      fedilink
      arrow-up
      1
      ·
      2 hours ago

      An RCD measures the difference in current flow between the phase and neutral, so it will trip in this scenario. An alternative path to earth is precisely what they’re designed to detect.

      • Norah (pup/it/she)@lemmy.blahaj.zone
        link
        fedilink
        English
        arrow-up
        2
        ·
        1 hour ago

        Ah yeah, you’re right, my mistake. It’s wild to me as an Aussie that they aren’t universal in the States. Plenty of houses (or outlets?) don’t have them IIRC?

        • Ilovethebomb@sh.itjust.works
          link
          fedilink
          arrow-up
          2
          ·
          1 hour ago

          Plenty of old houses still don’t have them in Australia and NZ, but they’re required on power circuits in new builds.

          As they should be, they’re an incredible technology.